FEATURES
- Maximum 556.0 kVA, 400 V, 1500 RPM
- 950 litre tank for 12 hrs @ 75% Load
- Industrial brushless alternator with AVR
- Steel baseframe, retention basin & fuel tank with sensor
- World wide after sales service and technical support
- Test report, manuals and electrical drawings supplied
- Modular design, open and silent version available
- Warranty
PERFORMANCE
Prime power (PRP) | 505.0 kVA |
Prime power (PRP) | 404.0 kW |
Standby power (LTP) | 556.0 kVA |
Standby power (LTP) | 444.8 kW |
Power factor | 0.8 |
Frequency (Hz) | 50 Hz |
Voltage (V) | 400 V |
GENERAL ENGINE DATA
Genset Controller | |
Engine brand | |
Engine model | TAD1641GE |
Cylinders | 6 |
Speed | 1500 RPM |
Cubic capacity | 16.12 |
Air intake | Turbocharged |
Standard voltage | 24 V |
SAE | 1-14 |
BMEP | 2133 |
Cooling | Water |
Flywheel P.R.P. | 430.0 kW |
Flywheel Stand-by | 473.0 kW |
EMISSIONS
TA Luft | Standard |
TA Luft2 | Not available |
EPA | Tier 2 |
Stage | Stage 2 |
GENERATOR DIMENSIONS
Length | 4500 mm |
Width | 1830 mm |
Height | 2300 mm |
Weight | 5200 kgs |
Tank Capacity | 950 l |
FUEL CONSUMPTION
Fuel Cons. at 110% | 112.0 l/h |
Fuel Cons. at 100% | 101.0 l/h |
Fuel Cons. at 75% | 75.0 l/h |
Fuel Cons. at 50% | 51.0 l/h |
Fuel Cons. at 25% | 30.0 l/h |
SPEED REGULATION
Electronic regulator | Standard |
Precision class | G3 |
ENGINE LIQUIDS
Oil quantity | 48.0 l |
Antifreeze quantity | 33.0 l |
HEAT FROM ENGINE
Heat from radiator | 30.0 kW |
Heat from exhaust | 326.0 kW |
Heat from radiation | 172.0 kW |
ALTERNATOR
Brand | MARELLI |
Model | MJB355SA4 |
Continuous Power | 560.0 kVA |
Standby Power | 510.0 kVA |
Connection | Series star |
Phases | Three phases with neutral |
Winding | 12 terminals 50-60Hz Winding M0 |
Terminal No | 12 |
IP Protection | 23 |
Regulator | M31FA600A |
Precision | 0.5 ± % |
HEAT FROM EXHAUST
Exhaust temperature | 475 °C |
Cooling air flow | 365.00 m³/min |
Combustion air flow | 32.00 m³/min |
Exhaust gas flow | 79.00 m³/min |
PLEASE NOTE: ALL ratings are approximate and at SEA LEVEL. Engines need to be de-rated for altitude. A rough guide to de-rate performance is 1% for every 100m above sea level. I.e: A 20kVA at sea level is an 18kVA at 1000m above sea level (10% less) etc.