DEEPSEA DSE6120-MK3

DeepSea DSE6120-MK3 Generator Controllers
DeepSea DSE6120-MK3 Controller

Description

The Deep Sea Electronics DSE6120 MKIII is an Auto Mains (Utility) Failure control module suitable for a wide variety of single diesel or gas genset applications. It monitors an extensive number of engine parameters and displays warnings, shutdown and engine status information on a back-lit LCD screen, illuminated LEDs and via remote PC.

The module also monitors the mains (utility) supply. It is compatible with electronic (CAN) and non-electronic (magnetic pick-up / alternator sensing) engines, includes a USB port and dedicated DSENet terminals for system expansion, and provides PLC functionality. Configuration is via the DSE Configuration Suite PC software, with selected front-panel editing also available.

Functions & Features

  • Automatic start and stopping of the generator and transfer of load based on mains (utility) availability
  • 3-phase generator and mains (utility) sensing with protection
  • Manual fascia control and automatic control by inputs and other functions
  • Compatible with electronic CAN engines and non-electronic magnetic pick-up / alternator-sensing engines
  • 6 configurable DC outputs
  • 8 configurable digital inputs
  • 4 configurable analogue/digital inputs
  • Internal PLC editor
  • Breaker control buttons on the front fascia
  • DSENet expansion compatibility
  • Data logging facility and configurable event log (100)
  • CAN, MPU and alternator speed sensing (selectable by engine type)
  • Tier 4 ECO engine support including exhaust fluids and filters
  • Fuel usage monitor and low-level alarms
  • Backed-up real-time clock
Remote Communication
  • USB port for DSE Configuration Suite PC software
  • DSENet expansion terminals for system expansion modules
Remote Communication Modules

Monitor and control your generator remotely with DeepSea-compatible communication modules.

View Remote Comms Options
Technical Parameters
SpecificationValue
Overall size216 mm x 158 mm x 43 mm
Panel cut-out184 mm x 137 mm
Maximum panel thickness8.0 mm
Weight0.5 kg
DC supply8 V to 35 V continuous (5 V for up to 1 minute)
Generator & mains voltage range15 V to 415 V AC (Ph to N); 26 V to 719 V AC (Ph to Ph)
Frequency range3.5 Hz to 75 Hz
Magnetic pick-up+/- 0.5 V to 70 V; 10,000 Hz max
Front protectionIP65 (with optional sealing gasket)
Product variant6120-05