DEEPSEA DSE6120-MK3
Description
The Deep Sea Electronics DSE6120 MKIII is an Auto Mains (Utility) Failure control module suitable for a wide variety of single diesel or gas genset applications. It monitors an extensive number of engine parameters and displays warnings, shutdown and engine status information on a back-lit LCD screen, illuminated LEDs and via remote PC.
The module also monitors the mains (utility) supply. It is compatible with electronic (CAN) and non-electronic (magnetic pick-up / alternator sensing) engines, includes a USB port and dedicated DSENet terminals for system expansion, and provides PLC functionality. Configuration is via the DSE Configuration Suite PC software, with selected front-panel editing also available.
Functions & Features
- Automatic start and stopping of the generator and transfer of load based on mains (utility) availability
- 3-phase generator and mains (utility) sensing with protection
- Manual fascia control and automatic control by inputs and other functions
- Compatible with electronic CAN engines and non-electronic magnetic pick-up / alternator-sensing engines
- 6 configurable DC outputs
- 8 configurable digital inputs
- 4 configurable analogue/digital inputs
- Internal PLC editor
- Breaker control buttons on the front fascia
- DSENet expansion compatibility
- Data logging facility and configurable event log (100)
- CAN, MPU and alternator speed sensing (selectable by engine type)
- Tier 4 ECO engine support including exhaust fluids and filters
- Fuel usage monitor and low-level alarms
- Backed-up real-time clock
- USB port for DSE Configuration Suite PC software
- DSENet expansion terminals for system expansion modules
Monitor and control your generator remotely with DeepSea-compatible communication modules.
View Remote Comms Options| Specification | Value |
|---|---|
| Overall size | 216 mm x 158 mm x 43 mm |
| Panel cut-out | 184 mm x 137 mm |
| Maximum panel thickness | 8.0 mm |
| Weight | 0.5 kg |
| DC supply | 8 V to 35 V continuous (5 V for up to 1 minute) |
| Generator & mains voltage range | 15 V to 415 V AC (Ph to N); 26 V to 719 V AC (Ph to Ph) |
| Frequency range | 3.5 Hz to 75 Hz |
| Magnetic pick-up | +/- 0.5 V to 70 V; 10,000 Hz max |
| Front protection | IP65 (with optional sealing gasket) |
| Product variant | 6120-05 |