Evolution Error Codes

DISPLAYED ALARM E-CODE BREAKDOWN DESCRIPTION NOTES
Controller Fault No E-code on HSB Replace Controller
Overcrank 1100 Condition - Engine Cranks but will not Start Unit turns over but will not start. Controller is receiving signal on Wire 18. Problem 17
Overspeed 1200 Prolonged Over 72 Hz for 3 seconds. Possible cause: Stepper motor/mixer body assembly issue. Test 12
Overspeed 1205 Instantaneous Over 75Hz for .1 second (100 milliseconds). Possible cause: Stepper motor/mixer body assembly issue. Test 12
Low Oil Pressure 1300 Occurred while running The default Extended alarm for low oilpressure. Check oil level and pressure. Test 61
High Temperature 1400 Condition - Air Flow Impeded I Flow Issue Check the inleUoutlet for debris. Test 62
RPM Sensor 1501 Twin Cylinder+Running Twin Cylinder Running faults to RPM sensor loss. Possible Causes: air pocket in fuel line. dirty fuel, missing ignition pulse (loss of one of the primary coils). Test 50 and Test 64
RPM Sensor 1505 Twin Cylinder+Cranking Twin Cylinder Cranking faults to RPM sensor loss Possible Cause: starter motor issue, missing ignition pulse (loss of one of the primary coils). If engine cranks, Test 64. If engine does not crank, Problem 15.
RPM Sensor 1511 Single Cylinder+Running Single Cylinder Running with Low Fuel Pressure faults to RPM sensor loss Possible Causes: air pocket in fuel line,dirty fuel. Test 50 and Test 64
RPM Sensor 1515 Single Cylinder+Cranking Single Cylinder Cranking faults to RPM sensor loss Possible Cause: starter motor issue. If engine cranks, Test 64. If engine does not crank, Problem 15.
Underspeed 1600 Condition - Unit is Overloaded Unit is Overloaded slowing engine speed, fuel supply low or throttle control problem. Problem 1, Test 50 or Test 12
Overvoltage 1800 Prolonged Over-Voltage Problem 2
Undervoltage 1900 Prolonged Under-Voltage Undervoltage due to loss of voltage for some time (10+ seconds). Test 5
Undervoltage 1901 Instantaneous Undervoltage due to sudden loss of voltage. Problem 1
Undervoltage 1902 Both Zero Crosses missing Undervoltage due to faulty excitation winding.or zero cross circuit.or circuit in general. Possible cause: loose wiring, field boost hardware failure Problem 1
Undervoltage 1906 Single Zero Cross missing Undervoltage due to faulty excitation winding , zero cross circuit, or circuit in general. Possible cause: field boost hardware failure Problem 1
Wiring Error 2099 Customer connection low voltage and high voltage wires are crossed. Check customer connection in generator
Overload Remove Load 2100 Overloaded - Default (Output Current Method) Unit is overloaded, one of the two CTs is detecting an overload condition. Check transfer switch loadshed functionality. (Change load dynamics or utilize loadshed). Remove Load
Undervoltage Overload 2299 Unit was overloaded and attempted to start with a large load connected. The unit can not ramp up the generator voltage to its normal target volt- age value if it starts with a large load connected Remove Load
Stepper Overcurrent 2399 Current flow in stepper coil(s ) above specification Test 12
Fuse Problem 2400 Missing I Damaged Fuse The 7.5 amp Controller Fuse is missing or blown (open). Test 44
Low Battery Condition-> Battery less than 12.1Volts for 60 seconds Test 45
Battery Problem Condition-> More than 16 Volts of battery voltage or 600 milliamperes or more of charge current at the end of an 18 hour charge Test 45
Charger Warning Less than 12.5 volts of battery voltage at the end of a 18 hour charge Problem 22
Charger Missing AC AC power is missing from the battery charger input Problem 22
SEEPROM Abuse Condition-> more than 1200 writes to the EEPROM in a 5 minute period.