Here is a full list of all the possible error codes on your Solax hybrid inverter.
| Error Message | Possible Reason | Possible Solution |
|---|---|---|
| Grid Fault | Grid is disconnected or voltage and frequency is out of range. | Inverter will automatically reconnect once mains power is back to normal. |
| No Utility | Grid is disconnected or possible cable disconnected. | Check the Grid-connection cable. |
| PV over Voltage | Bus Voltage from the solar panels is higher than the maximum voltage allowed. | 1. Disconnect PV+ & PV- and reconnect. 2. Reconfigure solar panels to correct voltage. |
| DC INJ High | DC input current higher than the set value. | Inverter will automatically once mains power is back to normal. |
| SCI Fault | The programming and debugging port is damaged. | 1. Disconnect PV+ & PV- and reconnect. 2. Replace. |
| AC Sensor Fault | During the Star Checking time, the current in Hall CT is too high | 1. Disconnect PV+ & PV- and reconnect. 2. Replace. |
| Isolation Fault | The impedance between PV+ & PV- and ground is too high. | 1. Disconnect PV+ & PV- and reconnect. 2. Replace. |
| Consistent Fault | There are 2 CPUs in the communication module. This is caused when these 2 CPUs cannot communicate or data is different. | 1. Disconnect PV+ & PV- and reconnect. 2. Replace. |
| Relay Fault | The internal relay is broken. | 1. Disconnect PV+ & PV- and reconnect. 2. Replace. |
| Ground Fault | Earth Leakage current is too high. | 1. Disconnect DC & AC input and reconnect. 2. Replace. |
| EEPROM Fault | The ROM in the internal circuit is faulty. | 1. Disconnect PV+ & PV- and reconnect. 2. Replace. |
| High DC Bus | Bus voltage is higher than the maximum value. | 1. Disconnect PV+ & PV- and reconnect. 2. Replace. |
| GFCI Fault | Earth Leakage protection. | Inverter will reconnect once mains power is back to normal. |
| SPI ERR | Spi communication fault inside the PCB board | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state it could be a hardware problem. |
| SCI ERR | SCI communication fault among the PCB boards | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state open the cover of the inverter to make sure all of the cables are secured. If the problem persists it could be a hardware problem. |
| LcdCommsErr | Communication error between LCD board and other Boards | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state open the cover of the inverter to make sure all of the cables are secured. If the problem persists it could be a hardware problem. |
| HW-OCP-ACR | Hardware has detected over current on R phase. | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check that the PV input current is not higher than rated value. If the problem persists it could be a hardware fault. |
| HW-OCP-ACS | Hardware has detected over current on S phase | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check that the PV input current is not higher than rated value. If the problem persists it could be a hardware fault. |
| HW-OCP-SCT | Hardware has detected over current on T phase. | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check that the PV input current is not higher than rated value. If the problem persists it could be a hardware fault. |
| HW-OVP-BUS | Hardware has detected BUS over voltage. | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check the PV voltage to see if it is higher than the nominal value. |
| HW-OCP-Boost1 | Hardware has detected Boost1 over current. | Disconnect PV+ & PV- and reconnect. If the problem persists it could be a hardware problem. |
| HW-OCP-Boost2 | Hardware has detected Boost2 over current. | Disconnect PV+ & PV- and reconnect. If the problem persists it could be a hardware problem. |
| PVConfigSet-Wrong | PV Configuration setting incorrect | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check the PV configuration setting. If each PV string's connected to DC input independently set to "Multi". If each PV string's connected to DC input together, set to "Comm". If problem persists it could be a hardware problem. |
| SampleConsistanntFault | The detection circuit faulty. | Disconnect PV+ & PV- and reconnect. If the problem persists it could be a hardware problem. |
| Unrecover-RelayFault | Relay fault. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| Current-Sensor-Fault | Current Sensor Fault. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| Unrecover-FANXFault | FAN circuit fault. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| EEPROM-WR-Fault | EEPROM reading or writing fault | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| GFCI-device-fault | Leakage current detection device fault. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| SW-OVP-ACR | Software detected over voltage on phase R. | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check the PV input voltage to make sure it is within range. If problem persists it could be a hardware problem. |
| SW-OVP-ACS | Software detected over voltage on phase S. | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check the PV input voltage to make sure it is within range. If problem persists it could be a hardware problem. |
| SW-OVP-ACT | Software detected over voltage on phase T. | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check the PV input voltage to make sure it is within range. If problem persists it could be a hardware problem. |
| SW-OCP-BOOST1 | Software detected Boost1 over current. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| SW-OCP-BOOST2 | Software detected Boost2 over current. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| PLL Fault | Phase-lock over time. | Mains supply could be unstable. Inverter will reconnect automatically. If the problem persists please check the grid-connection. |
| Grid-Lost –Fault | Grid voltage or frequency is out of range or missing. | Please check the grid voltage and frequency. Inverter will automatically reconnect once mains power is back to normal. |
| SW-OVP-AC | Over Voltage on AC side. | Disconnect PV+ & PV- and reconnect. If the inverter cannot return to normal state check the PV input voltage to see if it's within range. If problem persists it could be a hardware problem. |
| SW-OVP-BOOST1 | Software detected Boost1 over current. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| SW-OVP-BOOST2 | Software detected Boost2 over current. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| SW-OVP-BOOST | Software detected general boost over current. | Disconnect PV+ & PV- and reconnect. If problem persists it could be a hardware problem. |
| SW-OVR-ACR / SW-OVP-ACS / SW-OVP-ACT | Software detected over voltage of each phase on AC side. | Reboot inverter and wait to see if problem clears. If problem persists please check closest transformer. |
| SW-UVP-ACR / SW-UVP-ACS / SW-UVP-ACT | Software detected under voltage of each phase on AC side. | Reboot inverter and wait to see if problem clears. If problem persists please check closest transformer. |
| SW-OVP-BUS | Software detected BUS over voltage | Check PV input to ensure DC voltage is within range. |
| SW-OFP-AC | Software detected over frequency on any of the phases on the AC side. | Reboot inverter and wait to see if problem clears. If problem persists please check frequency value on inverter LCD. |
| SW_OFP_ACR / SW_OFP_ACS / SW_OFP_ACT | Over frequency of each phase on AC side. | Reboot inverter and wait to see if problem clears. If problem persists please check frequency value on inverter LCD. |
| SW_UFP_AC | Under frequency on any phase on AC side. | Reboot inverter and wait to see if problem clears. If problem persists please check frequency value on inverter LCD. |
| SW_UFP_ACR / SW_UFP_ACS / SW_UFP_ACT | Under frequency on each phase on AC side. | Reboot inverter and wait to see if problem clears. If problem persists please check frequency value on inverter LCD. |
| IsoIFault | Isolation fault in boost circuit 1 | Check inverter ground resistance and the PV ground resistance. |
| IsoIIFault | Isolation fault in boost circuit 2 | Check inverter ground resistance and PV ground resistance. |
| RelayShortFault | Relay fault | Replace the inverter. |
| RelayOpenFault | Relay fault | Replace the inverter. |
| SW_OCP_DCI | DCI Current over limit | Replace the inverter. |
| SW_OCP_RCD / SW_OCP_RCD_jumpI / SW_OCP_RCD_jumpII / SW_OCP_RCD_jumpIII / SW_OCP_RCD_300mA | Residual current detector device fault or residual current over limit. | Check all connections. Check for broken conductors. If problem persists replace inverter. |
| SW_OCP_ACRMS | Rms value of AC current is over limit. | Reboot inverter to see if problem clears. |
| SW_OverTemp | Temperature is over limit | Check if fan is running normally and check environmental temperature. |
| SW_IACRMS_UBANLANCE | The RMS value of AC current is unbalanced. | |
| SW_FANIFault / SW_FANIIFault / SW_FANIIIFault | Fan Fault | Check the Fan and replace if needed. |
| UnRecover_LN_Fault | The L & N line is not connected correctly. | Check connections. |
| SW_BUS_Unbalance | BUS is unbalanced. | Replace. |
| PhaseDeltaFault | Grid power unstable. | Reboot inverter to see if problem clears. |